Thermistor Wiring: How to Connect a Thermistor to a PLC
A PLC analog input can’t read a thermistor’s resistance directly. Wire the thermistor’s two leads to a thermistor-to-4-20mA transmitter, wire the transmitter in series with a DC supply and a spare 4-20mA analog input, then scale 4–20 mA to temperature in the PLC.
You’ve been asked to add a thermistor temperature measurement to a PLC system. General references such as Wikipedia explain the physics, but not how to finish the job – this guide gets you from sensor to working PLC reading.
What is a thermistor?
A thermistor is a low-cost, accurate temperature sensor whose electrical resistance changes with temperature – a sensor that turns a physical condition (temperature) into something you can measure. There are two types: NTC (resistance falls as temperature rises) and PTC (resistance rises). NTC thermistors are the most common for temperature measurement, and the 10K Ω at 25 °C curve is the industry standard.
Thermistors suit limited temperature ranges, where they can be more precise than other sensors – typical uses are HVAC, refrigeration and equipment cooling.
A bare bead thermistor is a low-cost, accurate way to read temperature – two wires, no polarity.
What can you connect to a PLC?
A stock PLC converts only a few analog input ranges to digital values – typically 4-20 mA, 0-10 V or 1-5 V. A thermistor gives none of these: it is a changing resistance, and its curve is not linear. That’s why a PLC can’t read a thermistor directly. Option cards for extra ranges exist, but they can be expensive, have long lead times, and need a PLC programmer – sticking to a range you already have is easier.
Using a generic range such as 4-20 mA needs a signal conditioner. Pair a thermistor with one – a thermistor transmitter – and you have a temperature transmitter, the standard way to bring temperature into a PLC. It powers the thermistor, linearises its curve and converts it to a 4-20 mA signal your existing input already reads. 4-20 mA also runs long cable distances without losing accuracy, and its “live zero” lets the PLC tell a broken loop (0 mA) from a real low reading – why 4-20 mA starts at 4 mA.
Most PLC analog inputs read 4-20 mA, 0-10 V or 1-5 V – not resistance.
How do I connect a thermistor to a PLC?
Three things to understand first: the sensor (its type and resistance curve), the signal conditioning (what turns it into a signal the PLC can read), and the connections (sensor, power and the measurement channel). Then:
- Choose the transmitter for your sensor and range. Match the thermistor curve (10K NTC) and the temperature span you need – standard ranges below.
- Wire the thermistor to the transmitter’s two input terminals. Thermistors have no polarity.
- Wire the 4-20 mA loop in series: DC supply (+) → transmitter (+) → transmitter (−) → PLC analog input (+) → input (−) → supply (−). The transmitter is loop powered (7.5–36 V DC), so there is no separate power wiring.
- Scale the signal in the PLC: Temperature = Low + (mA − 4) ÷ 16 × (High − Low). Example for −10 to 50 °C: 12 mA = −10 + 8 ÷ 16 × 60 = 20 °C.
Voltage input instead of current? Add a loop termination resistor across the input – 250 Ω turns 4-20 mA into 1-5 V. Before wiring, collect the cut sheets for the sensor, transmitter and PLC input card and put the setup on paper: terminal types vary by PLC, and the channel you use depends on which inputs are free.
A thermistor transmitter conditions the temperature sensor’s signal into something the PLC can measure.
Where can I get thermistor transmitters?
Right here – Robert Owen Inc. builds them. Pick your range and request a quote – also for quantities, purchase orders or a custom range. Full product details: 10K NTC thermistor temperature transmitter.
Ranges and prices
Pick the temperature span you need. Quantities, purchase orders and custom spans – request a quote.
| Range | Sensor | Output | Price | Order | Details |
|---|---|---|---|---|---|
| −10 to 50 °C | 10K NTC | 4-20 mA, 2-wire | $300 | Request a quote | View transmitter |
| 0 to 50 °C | 10K NTC | 4-20 mA, 2-wire | $300 | Request a quote | View transmitter |
| −10 to 75 °C | 10K NTC | 4-20 mA, 2-wire | $300 | Request a quote | View transmitter |
| 0 to 75 °C | 10K NTC | 4-20 mA, 2-wire | $300 | Request a quote | View transmitter |
| Other thermistors / custom span | 1K–100K NTC (e.g. 2.252K, 3K, 5K, 30K) | 4-20 mA, 2-wire | Quote | Request a quote | Built to order |
All four ranges on one page: 10K NTC to 4-20 mA transmitters · product listing: 10K NTC thermistor temperature transmitter.
Wireless and USB thermistor options

ROI-RFX-10K – wireless 10K NTC thermistor transmitter

ROI-USB-Thermistor – 4-channel USB thermistor recorder
| Product | Sensors | Output | Price | Order | Details |
|---|---|---|---|---|---|
| ROI-RFX-10K wireless thermistor transmitter a system uses at least 2 units | 10K NTC | 2.4 GHz wireless to a PC | $450 / unit | Request a quote | View product |
| ROI-USB-Thermistor recorder software included (download) | 4 × 10K NTC | USB to a Windows PC | $495 | Request a quote | View product |
| Multi-channel thermistor system | 10K NTC, 32+ points | Modbus RS-485 to PC / PLC | Quote | Request a quote | View system |
Transmitter specifications
- Input
- 10K NTC thermistor at 25 °C (1K–100K to order)
- Output
- 4-20 mA, loop powered, 2-wire
- Loop supply
- 7.5 to 36 V DC
- Response
- 10 ms
- Wire size
- 30–12 AWG
- Mounting
- 35 mm DIN rail or surface, snap-on base
- Size
- 4.510 × 1.258 × 3.948 in (L × W × H above rail)
Where it is used
- HVAC supply, return and space temperature
- Refrigeration and chillers
- Computer room and enclosure monitoring
- Environmental monitoring
- Dryers and other industrial processes
Thermistor wiring – common questions
Can I connect a thermistor directly to a PLC?
Only if the PLC has a special thermistor or resistance input card. Standard 4-20 mA or 0-10 V inputs need a thermistor transmitter in between.
Does a thermistor need 2-wire or 3-wire connection?
Two wires. A 10K thermistor’s resistance is so high that normal lead-wire resistance has very little effect, and thermistors have no polarity.
Can I read the 4-20 mA signal on a 0-10 V or 1-5 V input?
Yes. Put a loop termination resistor across the input: 250 Ω gives 1-5 V, 500 Ω gives 2-10 V.
How do I scale 4-20 mA to temperature?
Temperature = Low + (mA − 4) ÷ 16 × (High − Low). On a −10 to 50 °C transmitter, 4 mA = −10 °C, 12 mA = 20 °C and 20 mA = 50 °C.
What if my thermistor isn’t 10K?
Transmitters can be built for thermistors from 1K to 100K at 25 °C, with a custom output span. Contact us with the sensor and range.
Related guides and products
Many thermistors on one cable
Distributed NTC measurement: transmitters, I/O nodes and one RS-485 cable.
Multi-channel systems →Ready to add a thermistor to your PLC?
10K NTC to 4-20 mA transmitters in four standard ranges. Custom ranges and quantities on request. From a single sensor to hundreds, we connect sensors and software – signal conditioning, signal processing and data acquisition, including custom software.
Questions? Contact us – we look forward to answering them.