Thermistor Wiring: How to Connect a Thermistor to a PLC

Thermistor wiring guide

Thermistor Wiring: How to Connect a Thermistor to a PLC

A PLC analog input can’t read a thermistor’s resistance directly. Wire the thermistor’s two leads to a thermistor-to-4-20mA transmitter, wire the transmitter in series with a DC supply and a spare 4-20mA analog input, then scale 4–20 mA to temperature in the PLC.

ROI-XMA 10K NTC thermistor to 4-20mA transmitter on a DIN rail base

You’ve been asked to add a thermistor temperature measurement to a PLC system. General references such as Wikipedia explain the physics, but not how to finish the job – this guide gets you from sensor to working PLC reading.

What is a thermistor?

A thermistor is a low-cost, accurate temperature sensor whose electrical resistance changes with temperature – a sensor that turns a physical condition (temperature) into something you can measure. There are two types: NTC (resistance falls as temperature rises) and PTC (resistance rises). NTC thermistors are the most common for temperature measurement, and the 10K Ω at 25 °C curve is the industry standard.

Thermistors suit limited temperature ranges, where they can be more precise than other sensors – typical uses are HVAC, refrigeration and equipment cooling.

10K NTC bead thermistor temperature sensor with two leads

A bare bead thermistor is a low-cost, accurate way to read temperature – two wires, no polarity.

What can you connect to a PLC?

A stock PLC converts only a few analog input ranges to digital values – typically 4-20 mA, 0-10 V or 1-5 V. A thermistor gives none of these: it is a changing resistance, and its curve is not linear. That’s why a PLC can’t read a thermistor directly. Option cards for extra ranges exist, but they can be expensive, have long lead times, and need a PLC programmer – sticking to a range you already have is easier.

Using a generic range such as 4-20 mA needs a signal conditioner. Pair a thermistor with one – a thermistor transmitter – and you have a temperature transmitter, the standard way to bring temperature into a PLC. It powers the thermistor, linearises its curve and converts it to a 4-20 mA signal your existing input already reads. 4-20 mA also runs long cable distances without losing accuracy, and its “live zero” lets the PLC tell a broken loop (0 mA) from a real low reading – why 4-20 mA starts at 4 mA.

PLC with analog input module that accepts 4-20mA signals

Most PLC analog inputs read 4-20 mA, 0-10 V or 1-5 V – not resistance.

How do I connect a thermistor to a PLC?

Three things to understand first: the sensor (its type and resistance curve), the signal conditioning (what turns it into a signal the PLC can read), and the connections (sensor, power and the measurement channel). Then:

  1. Choose the transmitter for your sensor and range. Match the thermistor curve (10K NTC) and the temperature span you need – standard ranges below.
  2. Wire the thermistor to the transmitter’s two input terminals. Thermistors have no polarity.
  3. Wire the 4-20 mA loop in series: DC supply (+) → transmitter (+) → transmitter (−) → PLC analog input (+) → input (−) → supply (−). The transmitter is loop powered (7.5–36 V DC), so there is no separate power wiring.
  4. Scale the signal in the PLC: Temperature = Low + (mA − 4) ÷ 16 × (High − Low). Example for −10 to 50 °C: 12 mA = −10 + 8 ÷ 16 × 60 = 20 °C.

Voltage input instead of current? Add a loop termination resistor across the input – 250 Ω turns 4-20 mA into 1-5 V. Before wiring, collect the cut sheets for the sensor, transmitter and PLC input card and put the setup on paper: terminal types vary by PLC, and the channel you use depends on which inputs are free.

Thermistor wiring diagram: 10K NTC thermistor to 4-20mA transmitter input; transmitter in series with DC loop supply and PLC analog input
4-20mA loop circuit: a thermistor transmitter conditions the temperature sensor signal into a measurable 4-20mA current

A thermistor transmitter conditions the temperature sensor’s signal into something the PLC can measure.

Where can I get thermistor transmitters?

Right here – Robert Owen Inc. builds them. Pick your range and request a quote – also for quantities, purchase orders or a custom range. Full product details: 10K NTC thermistor temperature transmitter.

Thermistor transmitters

Ranges and prices

Pick the temperature span you need. Quantities, purchase orders and custom spans – request a quote.

RangeSensorOutputPriceOrderDetails
−10 to 50 °C10K NTC4-20 mA, 2-wire$300Request a quoteView transmitter
0 to 50 °C10K NTC4-20 mA, 2-wire$300Request a quoteView transmitter
−10 to 75 °C10K NTC4-20 mA, 2-wire$300Request a quoteView transmitter
0 to 75 °C10K NTC4-20 mA, 2-wire$300Request a quoteView transmitter
Other thermistors / custom span1K–100K NTC (e.g. 2.252K, 3K, 5K, 30K)4-20 mA, 2-wireQuoteRequest a quoteBuilt to order

All four ranges on one page: 10K NTC to 4-20 mA transmitters · product listing: 10K NTC thermistor temperature transmitter.

Wireless and USB thermistor options

ROI-RFX-10K wireless 2.4 GHz thermistor transmitter

ROI-RFX-10K – wireless 10K NTC thermistor transmitter

ROI-USB-Thermistor 4-channel USB thermistor recorder

ROI-USB-Thermistor – 4-channel USB thermistor recorder

ProductSensorsOutputPriceOrderDetails
ROI-RFX-10K wireless thermistor transmitter
a system uses at least 2 units
10K NTC2.4 GHz wireless to a PC$450 / unitRequest a quoteView product
ROI-USB-Thermistor recorder
software included (download)
4 × 10K NTCUSB to a Windows PC$495Request a quoteView product
Multi-channel thermistor system10K NTC, 32+ pointsModbus RS-485 to PC / PLCQuoteRequest a quoteView system

Transmitter specifications

Input
10K NTC thermistor at 25 °C (1K–100K to order)
Output
4-20 mA, loop powered, 2-wire
Loop supply
7.5 to 36 V DC
Response
10 ms
Wire size
30–12 AWG
Mounting
35 mm DIN rail or surface, snap-on base
Size
4.510 × 1.258 × 3.948 in (L × W × H above rail)

Where it is used

  • HVAC supply, return and space temperature
  • Refrigeration and chillers
  • Computer room and enclosure monitoring
  • Environmental monitoring
  • Dryers and other industrial processes

Thermistor wiring – common questions

Can I connect a thermistor directly to a PLC?

Only if the PLC has a special thermistor or resistance input card. Standard 4-20 mA or 0-10 V inputs need a thermistor transmitter in between.

Does a thermistor need 2-wire or 3-wire connection?

Two wires. A 10K thermistor’s resistance is so high that normal lead-wire resistance has very little effect, and thermistors have no polarity.

Can I read the 4-20 mA signal on a 0-10 V or 1-5 V input?

Yes. Put a loop termination resistor across the input: 250 Ω gives 1-5 V, 500 Ω gives 2-10 V.

How do I scale 4-20 mA to temperature?

Temperature = Low + (mA − 4) ÷ 16 × (High − Low). On a −10 to 50 °C transmitter, 4 mA = −10 °C, 12 mA = 20 °C and 20 mA = 50 °C.

What if my thermistor isn’t 10K?

Transmitters can be built for thermistors from 1K to 100K at 25 °C, with a custom output span. Contact us with the sensor and range.

Related guides and products

Thermistor wiring diagram

A full 4-20 mA thermistor transmitter wiring example.

See the diagram →

Thermocouple to a PLC

The same approach for thermocouple sensors.

Read the guide →

Many thermistors on one cable

Distributed NTC measurement: transmitters, I/O nodes and one RS-485 cable.

Multi-channel systems →

Ready to add a thermistor to your PLC?

10K NTC to 4-20 mA transmitters in four standard ranges. Custom ranges and quantities on request. From a single sensor to hundreds, we connect sensors and software – signal conditioning, signal processing and data acquisition, including custom software.

Questions? Contact us – we look forward to answering them.